Assume
you have a motor rated 500 HP, .95 power factor & 90 % efficiency
energized from a 4.16 Kv source, using a microprocessor motor
protection relay, provide the typical settings.
The
full load current can be taken from the motor nameplate as well as
the service factor. The motor full load current can be calculated
from the following: I = 500 (.746)/1.732 (4.16)(.85)(.9) =60 amps.